1887

oa Civil Engineering = Siviele Ingenieurswese - Measurements of live load on a temporary stand for spectators

 

Abstract

Tests are descriptionbed in which the live load on a temporary stand for spectators was measured during and after a major rugby football match. The greatest live load intensity recorded was 4,4 kPa (91 Ibf/ft2) on the gangway near to an exit from the seating area. This load intensity included a dynamic component of about 8 per cent. The maximum load intensity recorded underneath the seating area was 3,3 kPa (70 Ibf/ft2) including a dynamic component of about 5 per cent. The live load thus did not exceed the distributed load intensity of 4,8 kPa (100 Ibf/ft2) specified in the Standard Building Regulations as the minimum that such structures should be designed to support. Attention is, however, drawn to the possibility that the requirements of the Standard Building Regulations may not be sufficient for loads that might occur under abnormal conditions.

Loading

Article metrics loading...

/content/civeng/13/8/AJA10212019_18766
1971-08-01
2016-12-08
This is a required field
Please enter a valid email address
Approval was a Success
Invalid data
An Error Occurred
Approval was partially successful, following selected items could not be processed due to error